Setting Of Reverse Zone - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 8
Impedance protection
8.2.3.4
204
The impedance corresponding to the protected line, plus the first zone reach of the
shortest adjacent line.
The impedance corresponding to the protected line, plus the impedance of the
maximum number of transformers operating in parallel on the bus at the remote
end of the protected line.
Larger overreach than the mentioned 80% can often be acceptable due to fault current
infeed from other lines. This requires however analysis by means of fault calculations.
If any of the above gives a zone 2 reach less than 120%, the time delay of zone 2 must
be increased by approximately 200ms to avoid unwanted operation in cases when the
telecommunication for the short adjacent line at remote end is down during faults. The
zone 2 must not be reduced below 120% of the protected line section. The whole line
must be covered under all conditions.
The requirement that the zone 2 shall not reach more than 80% of the shortest adjacent
line at remote end is highlighted in the example below.
If a fault occurs at point F see figure 91, the IED at point A senses the impedance:
+
V
I
I
A
A
C
=
=
+
Z
Z
AF
AC
I
I
A
A
EQUATION302 V5 EN
A
I
A
Z<
IEC09000256 V2 EN
Figure 91:
Setting of overreaching zone

Setting of reverse zone

The reverse zone is applicable for purposes of scheme communication logic, current
reversal logic, weak-end infeed logic, and so on. The same applies to the back-up
protection of the bus bar or power transformers. It is necessary to secure, that it always
covers the overreaching zone, used at the remote line IED for the telecommunication
purposes.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
+
+
I
I
I
A
C
B
+
=
Z
R
CF
F
I
A
Z
Z
AC
CB
C
Z
CF
I
+ I
A
C
I
C
1MRK 502 071-UEN -
I
C
+
1
+
 ⋅
+
1
+
Z
Z
AC
C
F F
I
A
F
I
B
B
IEC09000256-2-en.vsd
Application manual
+
I
I
C
B
 ⋅
R
F
I
A
(Equation 59)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents