Section 15
Control
15.3.6.4
538
QB2OPTR (bay 1/sect.B1)
. . .
. . .
. . .
QB2OPTR (bay n/sect.B1)
VPQB2TR (bay 1/sect.B1)
. . .
. . .
. . .
VPQB2TR (bay n/sect.B1)
EXDU_DB (bay 1/sect.B1)
. . .
. . .
. . .
EXDU_DB (bay n/sect.B1)
IEC04000501 V1 EN
Figure 267:
Signals from double-breaker bays in section B1 to a bus-section
disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
QB2OPTR (bay 1/sect.B2)
. . .
. . .
. . .
QB2OPTR (bay n/sect.B2)
VPQB2TR (bay 1/sect.B2)
. . .
. . .
. . .
VPQB2TR (bay n/sect.B2)
EXDU_DB (bay 1/sect.B2)
. . .
. . .
. . .
EXDU_DB (bay n/sect.B2)
IEC04000502 V1 EN
Figure 268:
Signals from double-breaker bays in section B2 to a bus-section
disconnector

Signals in 1 1/2 breaker arrangement

If the busbar is divided by bus-section disconnectors, the condition for the busbar
disconnector bay no other disconnector connected to the bus-section must be made by
a project-specific logic.
The same type of module (A1A2_DC) is used for different busbars, that is, for both
bus-section disconnector A1A2_DC and B1B2_DC. But for B1B2_DC,
corresponding signals from busbar B are used.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
S1DC_OP
&
VPS1_DC
&
EXDU_BB
&
en04000501.vsd
S2DC_OP
&
VPS2_DC
&
EXDU_BB
&
en04000502.vsd