Section 16
Logic
16.12
16.12.1
16.12.2
16.12.3
616
Name of OUTx
Type
OUT9
BOOLEAN
OUT10
BOOLEAN
OUT11
BOOLEAN
OUT12
BOOLEAN
OUT13
BOOLEAN
OUT14
BOOLEAN
OUT15
BOOLEAN
OUT16
BOOLEAN
The sum of the numbers in column "Value when activated" when all OUTx (1≤x≤16)
are active equals 65535. This is the highest integer that can be converted by the
ITBGAPC function block.

Pulse integrator TIGAPC

Identification
Function description
Pulse integrator
Application
The pulse integrator function TIGAPC is intended for applications where there is a
need for a integration of a pulsed signal. For example, the pulses from the start output
of certain functions, like reverse power, loss of excitation and pole slip. Some
applications may require the integration of the start output of those functions to
perform the trip.
Setting guidelines
The pulse integrator function provides settings for time delay to operate and time
delay to reset. The time delay to operate setting is evaluated for activation of the output
and there will be no output until the integration of the input pulses equals this setting.
The output will be deactivated when the input signal is deactivated and the time delay
to reset has elapsed.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Description
Value when
activated
Output 9
256
Output 10
512
Output 11
1024
Output 12
2048
Output 13
4096
Output 14
8192
Output 15
16384
Output 16
32768
IEC 61850
IEC 60617
identification
identification
TIGAPC
1MRK 502 071-UEN -
Value when
deactivated
0
0
0
0
0
0
0
0
ANSI/IEEE C37.2
device number
Application manual

Hide quick links: