Settings For Rs485 And Optical Serial Communication - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
20.6.2.1
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Settings for RS485 and optical serial communication

General settings
SPA, DNP and IEC 60870-5-103 can be configured to operate on the SLM optical
serial port while DNP and IEC 60870-5-103 additionally can utilize the RS485 port.
A single protocol can be active on a given physical port at any time.
Two different areas in the HMI are used to configure the IEC 60870-5-103 protocol.
1.
The port specific IEC 60870-5-103 protocol parameters are configured under:
Main menu/Configuration/Communication/Station Communication/
IEC60870-5-103/
<config-selector>
SlaveAddress
BaudRate
RevPolarity (optical channel only)
CycMeasRepTime
MasterTimeDomain
TimeSyncMode
EvalTimeAccuracy
EventRepMode
CmdMode
RepIntermediatePos
<config-selector> is:
"OPTICAL103:1" for the optical serial channel on the SLM
"RS485103:1" for the RS485 port
2.
The protocol to activate on a physical port is selected under:
Main menu/Configuration/Communication/Station Communication/Port
configuration/
RS485 port
RS485PROT:1 (off, DNP, IEC103)
SLM optical serial port
PROTOCOL:1 (off, DNP, IEC103, SPA)
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
Figure 338:
Settings for IEC 60870-5-103 communication
Station communication
GUID-CD4EB23C-65E7-4ED5-AFB1-A9D5E9EE7CA8 V3 EN
Section 20
707