Section 15
Control
490
The connections are similar in all SESRSYN functions, apart from the breaker
position indications. The physical analog connections of voltages and the connection
to the IED and SESRSYN function blocks must be carefully checked in PCM600. In
all SESRSYN functions the connections and configurations must abide by the
following rules: Normally apparatus position is connected with contacts showing both
open (b-type) and closed positions (a-type).
WA1_QA1:
•
B1QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting CBConfig = 1 1/2 bus CB
TIE_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of WA2_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting CBConfig = Tie CB
WA2_QA1:
•
B1QOPEN/CLD = Position of WA1_QA1 breaker and belonging disconnectors
•
B2QOPEN/CLD = Position of TIE_QA1 breaker and belonging disconnectors
•
LN1QOPEN/CLD = Position of LINE1_QB9 disconnector
•
LN2QOPEN/CLD = Position of LINE2_QB9 disconnector
•
UB1OK/FF = Supervision of WA1_MCB fuse
•
UB2OK/FF = Supervision of WA2_MCB fuse
•
ULN1OK/FF = Supervision of LINE1_MCB fuse
•
ULN2OK/FF = Supervision of LINE2_MCB fuse
•
Setting CBConfig = 1 1/2 bus alt. CB
If only two SESRSYN functions are provided in the same IED, the connections and
settings are according to the SESRSYN functions for WA1_QA1 and TIE_QA1.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
Application manual