ABB REG670 Applications Manual page 528

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 15
Control
522
For bus-coupler bay n, these conditions are valid:
QB12OPTR (bay 1)
QB12OPTR (bay 2)
. . .
. . .
QB12OPTR (bay n-1)
VPQB12TR (bay 1)
VPQB12TR (bay 2)
. . .
. . .
VPQB12TR (bay n-1)
EXDU_12 (bay 1)
EXDU_12 (bay 2)
. . .
. . .
EXDU_12 (bay n-1)
IEC04000481 V1 EN
Figure 247:
Signals from any bays in bus-coupler bay n
If the busbar is divided by bus-section disconnectors into bus-sections, the signals
BBTR are connected in parallel - if both bus-section disconnectors are closed. So for
the basic project-specific logic for BBTR above, add this logic:
Section 1
(WA1)A1
(WA2)B1
(WA7)C
ABC_LINE
IEC04000482 V1 EN
Figure 248:
Busbars divided by bus-section disconnectors (circuit breakers)
The following signals from each bus-section disconnector bay (A1A2_DC) are
needed. For B1B2_DC, corresponding signals from busbar B are used. The same type
of module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnector A1A2_DC and B1B2_DC.
Signal
DCOPTR
The bus-section disconnector is open.
VPDCTR
The switch status of bus-section disconnector DC is valid.
EXDU_DC
No transmission error from the bay that contains the above information.
If the busbar is divided by bus-section circuit breakers, the signals from the bus-
section coupler bay (A1A2_BS), rather than the bus-section disconnector bay
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
&
&
&
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
ABC_LINE
1MRK 502 071-UEN -
BBTR_OP
VP_BBTR
EXDU_12
en04000481.vsd
Section 2
ABC_BC
AB_TRAFO
en04000482.vsd
Application manual
A2
B2
C