ABB REG670 Applications Manual page 123

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
IEC140000126 V2 EN
Figure 46:
PMUREPORT settings in PCM600 PST
Figure
47
shows an example of correct connection of SMAI and PHASORREPORT
blocks in ACT where two different SMAI blocks are connected to different
PHASORREPORT blocks with different instance numbers. In this example, as the
PHASORREPORT blocks have different instance numbers and different settings for
SvcClass and ReportRate, a separate SMAI block is used for each PHASORREPORT
block.
IEC140000127 V2 EN
Figure 47:
An example of correct connection of SMAI and PHASORREPORT
blocks in ACT
Figure
48
shows an example of wrong connection of SMAI and PHASORREPORT
blocks in ACT where the same SMAI block is connected to different
PHASORREPORT blocks with different instance numbers. Such connection will be
only correct if both connected PHASORREPORT blocks have similar settings for
SvcClass and ReportRate. If settings for PMUREPORT instances differ for SvcClass
or ReportRate, then PHASOR1 connection in PHASORREPORT1 instance 2 will not
Wide area measurement system
Section 6
IEC140000126-2-en.vsd
IEC140000127-2-en.vsd
117