ABB REG670 Applications Manual page 282

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 8
Impedance protection
276
Synchronous
Synchronous
machine 1
machine 1
SM1
SM1
E1
E1
U, I
U, I
E1
E1
Centre of oscillation
Centre of oscillation
IEC10000107 V1 EN
Figure 143:
The centre of electromechanical oscillation
The center of the electromechanical oscillation can be in the generator unit (or
generator-transformer unit) or outside, somewhere in the power system. When the
center of the electromechanical oscillation occurs within the generator it is essential
to trip the generator immediately. If the center of the electromechanical oscillation is
outside any of the generators in the power system, the power system should be split
into two different parts; so each part may have the ability to restore stable operating
conditions. This is sometimes called "islanding". The objective of islanding is to
prevent an out-of-step condition from spreading to the healthy parts of the power
system. For this purpose, uncontrolled tripping of interconnections or generators must
be prevented. It is evident that a reasonable strategy for out-of-step relaying as well as,
appropriate choice of other protection relays, their locations and settings require
detailed stability studies for each particular power system and/or subsystem. On the
other hand, if severe swings occur, from which a fast recovery is improbable, an
attempt should be made to isolate the affected area from the rest of the system by
opening connections at predetermined points. The electrical system parts swinging to
each other can be separated with the lines closest to the center of the power swing
allowing the two systems to be stable as separated islands. The main problem involved
with systemic islanding of the power system is the difficulty, in some cases, of
predicting the optimum splitting points, because they depend on the fault location and
the pattern of generation and load at the respective time. It is hardly possible to state
general rules for out-of-step relaying, because they shall be defined according to the
particular design and needs of each electrical network. The reason for the existence of
two zones of operation is selectivity, required for successful islanding. If there are
several out-of-step relays in the power system, then selectivity between separate
relays is obtained by the relay reach (for example zone 1) rather then by time grading.
The out-of-step condition of a generator can be caused by different reasons. Sudden
events in an electrical power system such as large changes in load, fault occurrence or
slow fault clearance, can cause power oscillations, that are called power swings. In a
non-recoverable situation, the power swings become so severe that the synchronism
is lost: this condition is called pole slipping.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
Synchronous
Synchronous
machine 2
machine 2
SM2
SM2
Voltages of all
Voltages of all
E2
E2
phases to
phases to
earth are zero
earth are zero
in the centre
in the centre
of oscillation
of oscillation
E2
E2
IEC10000107-1-en.vsd
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents