ABB REG670 Applications Manual page 430

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 10
Voltage protection
424
Table 47:
Settings
U/f op (%)
Timer
105
t1
112
t2
119
t3
126
t4
133
t5
140
t6
Information on the cooling time constant T
transformer manufacturer.
V/Hz
%
150
140
130
120
110
100
0.05
0.1
0.2
0.5
t6
t5
t4
IEC01000377 V1 EN
Figure 209:
Example on overexcitation capability curve and V/Hz protection
settings for power transformer
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Time set (s)
7200 (max)
600
60
20
8
4
should be retrieved from the power
cool
transformer capability curve
relay operate characteristic
1
2
5
10
t3
t2
1MRK 502 071-UEN -
Continous
20
50
100
200
(minutes)
t1
en01000377.vsd
Application manual
Time