Section 5
Local HMI
5.4.2
100
Table 12:
Trip LED (red)
LED state
Description
Off
On
Flasing
Alarm indicators
The 15 programmable three-color LEDs are used for alarm indication. An individual
alarm/status signal, connected to any of the LED function blocks, can be assigned to
one of the three LED colors when configuring the IED.
Table 13:
Alarm indications
LED state
Description
Off
Normal operation. All activation signals are off.
On
Follow-S sequence: The activation signal is on.
LatchedColl-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
LatchedAck-F-S sequence: The indication has been acknowledged, but the
activation signal is still on.
LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
LatchedReset-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
Flashing
Follow-F sequence: The activation signal is on.
LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication
has not been acknowledged.
LatchedAck-S-F sequence: The indication has been acknowledged, but the
activation signal is still on.

Parameter management

The LHMI is used to access the relay parameters. Three types of parameters can be
read and written.
Numerical values
String values
Enumerated values
Numerical values are presented either in integer or in decimal format with minimum
and maximum values. Character strings can be edited character by character.
Enumerated values have a predefined set of selectable values.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Normal operation.
A protection function has tripped. An indication message is displayed if the
auto-indication feature is enabled in the local HMI.
The trip indication is latching and must be reset via communication, LHMI or
binary input on the LEDGEN component. To open the reset menu on the
LHMI, press
.
Configuration mode.
1MRK 502 071-UEN -
Application manual