Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Security
Authority status ATHSTAT
Application
Authority status (ATHSTAT) function is an indication function block, which informs
about two events related to the IED and the user authorization:
the fact that at least one user has tried to log on wrongly into the IED and it was
blocked (the output USRBLKED)
the fact that at least one user is logged on (the output LOGGEDON)
The two outputs of ATHSTAT function can be used in the configuration for different
indication and alarming reasons, or can be sent to the station control for the same
purpose.
Self supervision with internal event list INTERRSIG
Application
The protection and control IEDs have many functions included. The included self-
supervision with internal event list function block provides good supervision of the
IED. The fault signals make it easier to analyze and locate a fault.
Both hardware and software supervision is included and it is also possible to indicate
possible faults through a hardware contact on the power supply module and/or
through the communication.
Internal events are generated by the built-in supervisory functions. The supervisory
functions supervise the status of the various modules in the IED and, in case of failure,
a corresponding event is generated. Similarly, when the failure is corrected, a
corresponding event is generated.
Apart from the built-in supervision of the various modules, events are also generated
when the status changes for the:
built-in real time clock (in operation/out of order).
external time synchronization (in operation/out of order).
Section 22
Security
719