Connecting and setting voltage inputs

The SIM module of REX060 has two analog output channels that shall be connected
to two voltage input channels of the IED.
If both stator and rotor protection are used, there are two possible methods to perform
the connection.
1.
The recommended connection requires four analog channels of the IED: two IED
voltage channels are used for the measured quantities for STTIPHIZ; two more
IED voltage channels are used for the measured quantities for ROTIPHIZ.
IED
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
VOLTAGE MEASURE (U)
CURRENT MEASURE (U)
IEC11000209 V1 EN
Figure 163:
Separate analogue inputs for stator (STTIPHIZ) and rotor
(ROTIPHIZ) protection
2.
It is possible to use a mixed connection that requires only two IED voltage
channels for both ROTIPHIZ and STTIPHIZ. REX060 outputs are connected in
series. This connection is not recommended and can be used only in applications
where it is proved the possibility to use it. The use of this connection leads to
reduced performances of both ROTIPHIZ and STTIPHIZ.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
Note
Default value
X61
8
9
STATOR MODULE SIM
10
11
X81
8
9
ROTOR MODULE RIM
10
11
REX060
IEC11000209-1-en.vsd
Application manual