Setting The Reach With Respect To Load - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 8
Impedance protection
8.2.3.6
206
Z
0
m
= -
K
0 1
×
+
+
2
Z
1
Z
0
R
f
EQUATION1426 V1 EN
If the denominator in equation
real and imaginary part of the reach reduction factor for the overreaching zones can be
written as:
×
X m
0
Re
( )
= -
Re
K
0
1
( )
2
+
Re
B
Im
EQUATION1427 V2 EN
( )
×
( )
X m
0
Im
=
Im
K
0
( )
2
+
Re
B
Im
EQUATION1428 V2 EN
Parallel line is out of service and earthed in both ends
Apply the same measures as in the case with a single set of setting parameters. This
means that an underreaching zone must not overreach the end of a protected circuit for
the single phase-to-earth faults.
Set the values of the corresponding zone (zero-sequence resistance and reactance)
equal to:
2
æ
X
m0
×
ç
------------------------- -
R
=
R
1
+
0E
0
2
è
R
+
X
0
0
EQUATION561 V1 EN
2
æ
X
m0
×
X
=
X
ç
1
------------------------- -
0E
0
2
è
R
+
X
0
0
EQUATION562 V1 EN

Setting the reach with respect to load

Set separately the expected fault resistance for phase-to-phase faults RFPPZx and for
the phase-to-earth faults RFPEZx for each zone. For each distance zone, set all
remaining reach setting parameters independently of each other.
The final reach in the resistive direction for phase-to-earth fault loop measurement
automatically follows the values of the line-positive and zero-sequence resistance,
and at the end of the protected zone is equal to equation 68.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
63
is called B and Z0m is simplified to X0m, then the
( )
B
( )
2
B
B
( )
2
B
ö
÷
2
ø
ö
÷
2
ø
1MRK 502 071-UEN -
(Equation 63)
(Equation 64)
(Equation 65)
(Equation 66)
(Equation 67)
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents