Interlocking For Double Cb Bay Db - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
15.3.8
15.3.8.1
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Section 1
(WA1)A1
(WA2)B1
BB_ES
BH_LINE
IEC04000512 V1 EN
Figure 278:
Busbars divided by bus-section disconnectors (circuit breakers)
The project-specific logic are the same as for the logic for the double busbar
configuration described in section "Signals in single breaker arrangement".
Signal
BB_DC_OP
All disconnectors on this part of the busbar are open.
VP_BB_DC
The switch status of all disconnectors on this part of the busbar is valid.
EXDU_BB
No transmission error from any bay that contains the above information.

Interlocking for double CB bay DB

Application
The interlocking for a double busbar double circuit breaker bay including
DB_BUS_A, DB_BUS_B and DB_LINE functions are used for a line connected to a
double busbar arrangement according to figure 279.
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BH_LINE
Section 15
Control
A2
B2
BB_ES
en04000512.vsd
545