ABB REG670 Applications Manual page 74

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 4
Analog inputs
68
Transformer
Transformer and
Line protection
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
IEC05000462 V2 EN
Figure 15:
Example how to set CTStarPoint parameters in the IED
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
IED
Setting of current input
for transformer functions:
Set parameter
CTStarPoint with
Transformer as
reference object.
Correct setting is
"ToObject"
1MRK 502 071-UEN -
Line
Reverse
Forward
Definition of direction
for directional
line functions
Setting of current input
for line functions:
Set parameter
CTStarPoint with
Line as
reference object.
Correct setting is
"FromObject"
Application manual