C37.118 Phasor Measurement Data Streaming Protocol Configuration Pmuconf - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
Section 6
6.1
6.1.1
6.1.2
6.1.3
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Wide area measurement system
C37.118 Phasor Measurement Data Streaming
Protocol Configuration PMUCONF
Identification
Function description
Configuration parameters for IEEE 1344
and C37.118 protocol
Application
The IED supports the following IEEE synchrophasor standards:
IEEE 1344-1995 (Both measurements and data communication)
IEEE Std C37.118-2005 (Both measurements and data communication)
IEEE Std C37.118.1–2011 and C37.118.1a-2014 (Measurements)
IEEE Std C37.118.2-2011 (Data communication)
PMUCONF contains the PMU configuration parameters for both IEEE C37.118 and
IEEE 1344 protocols. This means all the required settings and parameters in order to
establish and define a number of TCP and/or UDP connections with one or more PDC
clients (synchrophasor client). This includes port numbers, TCP/UDP IP addresses,
and specific settings for IEEE C37.118 as well as IEEE 1344 protocols.
Operation principle
The Figure
38
demonstrates the communication configuration diagram. As can be
seen, the IED can support communication with maximum 8 TCP clients and 6 UDP
client groups, simultaneously. Every client can communicate with only one instance
of the two available PMUREPORT function block instances at a time. It means that
one client cannot communicate with both PMUREPORT:1 and PMUREPORT:2 at
the same time. However, multiple clients can communicate with the same instance of
PMUREPORT function block at the same time. For TCP clients, each client can
decide to communicate with an existing instance of PMUREPORT by knowing the
corresponding PMU ID for that PMUREPORT instance. Whereas, for UDP clients,
the PMUREPORT instance for each UDP channel is defined by the user in the PMU
and the client has to know the PMU ID corresponding to that instance in order to be
Wide area measurement system
IEC 61850
IEC 60617
identification
identification
PMUCONF
-
Section 6
ANSI/IEEE C37.2
device number
-
103