Loss of excitation

Inadvertent generator energization

When the generator is taken out of service, and non-rotating, there is a risk that the
generator circuit breaker is closed by mistake.
Three-phase energizing of a generator, which is at standstill or on turning gear, causes
it to behave and accelerate similarly to an induction motor. The machine, at this point,
essentially represents the subtransient reactance to the system and it can be expected
to draw from one to four per unit current, depending on the equivalent system
impedance. Machine terminal voltage can range from 20% to 70% of rated voltage,
again, depending on the system equivalent impedance (including the block
transformer). Higher quantities of machine current and voltage (3 to 4 per unit current
and 50% to 70% rated voltage) can be expected if the generator is connected to a strong
system. Lower current and voltage values (1 to 2 per unit current and 20% to 40% rated
voltage) are representative of weaker systems.
Since a generator behaves similarly to an induction motor, high currents will develop
in the rotor during the period it is accelerating. Although the rotor may be thermally
damaged from excessive high currents, the time to damage will be on the order of a
few seconds. Of more critical concern, however, is the bearing, which can be damaged
in a fraction of a second due to low oil pressure. Therefore, it is essential that high
speed tripping is provided. This tripping should be almost instantaneous (< 100 ms).
There is a risk that the current into the generator at inadvertent energization will be
limited so that the "normal" overcurrent or underimpedance protection will not detect
the dangerous situation. The delay of these protection functions might be too long. The
reverse power protection might detect the situation but the operation time of this
protection is normally too long.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062