Setting Guidelines - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
20.2.2
20.2.3
20.2.3.1
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:
Operation: User can set IEC 61850 communication to On or Off.
GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sent
and received. This is only valid for Edition 1 and can be ignored if Edition 2 is used.
For Edition 2, the Ethernet link selection is done with the Ethernet Configuration Tool
(ECT) in PCM600.
Horizontal communication via GOOSE
Sending data
In addition to the data object and data attributes of the logical nodes, it is possible to
send the outputs of the function blocks using the generic communication blocks. The
outputs of this function can be set in a dataset and be sent in a GOOSE Control Block
to other subscriber IEDs. There are different function blocks for different type of
sending data.
Generic communication function for Single Point indication SPGAPC,
SP16GAPC
Application
Generic communication function for Single Point Value (SPGAPC) function is used
to send one single logical output to other systems or equipment in the substation.
SP16GAPC can be used to send up to 16 single point values from the application
functions running in the same cycle time. SPGAPC has one visible input and
SPGAPC16 has 16 visible inputs that should be connected in the ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for measured values (MVGAPC) function is used to
send the instantaneous value of an analog signal to other systems or equipment in the
substation. It can also be used inside the same IED, to attach a RANGE aspect to an
analog value and to permit measurement supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value
(MVGAPC) function allows the user to choose a deadband and a zero deadband for
the monitored signal. Values within the zero deadband are considered as zero.
Section 20
Station communication
683

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents