ABB REG670 Applications Manual page 576

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 15
Control
Table 58:
Setting of TxRXOP
TrfId=T1
T1RXOP=
Off
TrfId=T2
T1RXOP=
On
TrfId=T3
T1RXOP=
On
570
Signal
Explanation
reacSec
Transformer reactance in primary ohms referred to the LV side
relativePosition
The transformer's actual tap position
voltage Setpoint
The transformer's set voltage (
Manual configuration of VCTR GOOSE data set is required. Note that
both data value attributes and quality attributes have to be mapped.
The following data objects must be configured:
BusV
LodAIm
LodARe
PosRel
SetV
VCTRStatus
X2
The transformers controlled in parallel with the circulating current method or the
master-follower method must be assigned unique identities. These identities are
entered as a setting in each TR8ATCC, and they are predefined as T1, T2, T3,..., T8
(transformers 1 to 8). In figure
TrfId set to T1, T2 and T3, respectively.
For parallel control with the circulating current method or the master-follower method
alternatively, the same type of data set as described above, must be exchanged
between two TR8ATCC. To achieve this, each TR8ATCC is transmitting its own data
set on the output ATCCOUT as previously mentioned. To receive data from the other
transformers in the parallel group, the output ATCCOUT from each transformer must
be connected (via GOOSE or internally in the application configuration) to the inputs
HORIZx (x = identifier for the other transformers in the parallel group) on TR8ATCC
function block. Apart from this, there is also a setting in each TR8ATCC =/,..., =/
T1RXOP=Off/On,..., T8RXOP=Off/ On. This setting determines from which of the
other transformer individuals that data shall be received. Settings in the three
TR8ATCC blocks for the transformers in figure 291, would then be according to the
table 58:
T2RXOP=
T3RXOP=
On
On
T2RXOP=
T3RXOP=
Off
On
T2RXOP=
T3RXOP=
On
Off
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
USet ) for automatic control
291
there are three transformers with the parameter
T4RXOP=
T5RXOP=
Off
Off
T4RXOP=
T5RXOP=
Off
Off
T4RXOP=
T5RXOP=
Off
Off
1MRK 502 071-UEN -
T6RXOP=
T7RXOP=
Off
Off
T6RXOP=
T7RXOP=
Off
Off
T6RXOP=
T7RXOP=
Off
Off
Application manual
T8RXOP=
Off
T8RXOP=
Off
T8RXOP=
Off