Remote communication
718
one of the two possible local currents is transmitted
sum of the two local currents is transmitted
channel is used as a redundant backup channel
1½ breaker arrangement has two local currents, and the Current Transformer (CT)
earthing for those can differ. CT-SUM transmits the sum of the two CT groups. CT-
DIFF1 transmits CT group 1 minus CT group 2 and CT-DIFF2 transmits CT group 2
minus CT group 1.
CT-GRP1 and CT-GRP2 transmit the respective CT groups, and setting
RedundantChannel determines that the channel is used as a redundant backup
channel. The redundant channel takes the CT group setting of the main channel.
RemAinLatency corresponds to LocAinLatency set in the remote IED.
AnalogLatency specifies the time delay (number of samples) between actual sampling
and the time the sample reaches LDCM. The value is set to 2 when transmitting analog
data. When a merging unit according to IEC 61850-9-2 is used instead of the TRM,
this parameter shall be set to 5.
CompRange value indicates the current peak value over which truncation is made. To
set this value, knowledge of fault current levels is required. It is recommended to set
the minimum range that will cover the expected fault current value. For example, if a
40kA fault level is expected on the network, the 0-50kA settings range should be
chosen.
2 Mbit mode specific settings
RedundantCh is used to set the channel as a redundant backup channel. The redundant
channel takes the CT group setting of the main channel, and ignores the CT group
configured in its own transmit block.
LinkForwarded is used to configure the LDCM to merge the inter-trip and block
signals from another LDCM-receiver. This is used when the analog signals for the
LDCM-transmitter is connected to the receiver of another LDCM.