Section 7
Differential protection
7.4.2.1
176
The restricted earth fault protection is not affected, as a differential protection, with
the following power transformer related phenomena:
magnetizing inrush currents
overexcitation magnetizing currents
load tap changer
external and internal phase faults which do not involve earth
symmetrical overload conditions
Due to its features, REFPDIF is often used as a main protection of the transformer
winding for all faults involving earth.

Transformer winding, solidly earthed

The most common application is on a solidly earthed transformer winding. The
connection is shown in Figure 72.
REFPDIF
I3PW1CT1
IdN/I
I3P
IEC09000109-4-EN V2 EN
Figure 72:
Connection of the low impedance Restricted earth fault function
REFPDIF for a directly (solidly) earthed transformer winding
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 071-UEN -
Protected
winding
IEC09000109-4-EN.vsd
Application manual