Section 9
Current protection
9.12.2.1
388
To provide an effective protection for the generator for external unbalanced
conditions, NS2PTOC is able to directly measure the negative sequence current.
NS2PTOC also have a time delay characteristic which matches the heating
characteristic of the generator I
where:
I
is negative sequence current expressed in per unit of the rated generator current
2
t
is operating time in seconds
K
is a constant which depends of the generators size and design
2
A wide range of I
t settings is available, which provide the sensitivity and capability
2
necessary to detect and trip for negative sequence currents down to the continuous
capability of a generator.
A separate output is available as an alarm feature to warn the operator of a potentially
dangerous situation.

Features

Negative-sequence time overcurrent protection NS2PTOC is designed to provide a
reliable protection for generators of all types and sizes against the effect of unbalanced
system conditions.
The following features are available:
Two steps, independently adjustable, with separate tripping outputs.
Sensitive protection, capable of detecting and tripping for negative sequence
currents down to 3% of rated generator current with high accuracy.
Two time delay characteristics:
Definite time delay
Inverse time delay
The inverse time overcurrent characteristic matches
the generators.
Wide range of settings for generator capability constant K is provided, from 1 to
99 seconds, as this constant may vary greatly with the type of generator.
Minimum operate time delay for inverse time characteristic, freely settable. This
setting assures appropriate coordination with, for example, line protections.
Maximum operate time delay for inverse time characteristic, freely settable.
Inverse reset characteristic which approximates generator rotor cooling rates and
provides reduced operate time if an unbalance reoccurs before the protection
resets.
Service value that is, measured negative sequence current value, in primary
Amperes, is available through the local HMI.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
2
t = K as defined in standard.
2
1MRK 502 071-UEN -
2
=
I t
K
capability curve of
2
Application manual