1MRK 502 071-UEN -
9.5.3.2
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
For ANSI inverse time delay characteristics all three types of reset time characteristics
are available; instantaneous (1), IEC (2 = set constant time reset) and ANSI (3 =
current dependent reset time).
For IEC inverse time delay characteristics the possible delay time settings are
instantaneous (1) and IEC (2 = set constant time reset).
For the programmable inverse time delay characteristics all three types of reset time
characteristics are available; instantaneous (1), IEC (2 = set constant time reset) and
ANSI (3 = current dependent reset time). If the current dependent type is used settings
pr, tr and cr must be given.
tPCrvx, tACrvx, tBCrvx, tCCrvx: Parameters for programmable inverse time
characteristic curve. The time characteristic equation is according to equation 192:
æ
ç
A
ç
[ ] =
+
t s
ç
p
æ
ö
i
-
C
ç
÷
ç
è
>
ø
è
in
EQUATION1189 V1 EN
Further description can be found in the Technical reference manual (TRM).
tPRCrvx, tTRCrvx, tCRCrvx: Parameters for customer creation of inverse reset time
characteristic curve. Further description can be found in the Technical Reference
Manual.

Common settings for all steps

x means step 1, 2, 3 and 4.
AngleRCA: Relay characteristic angle given in degrees. This angle is defined as shown
in figure 180. The angle is defined positive when the residual current lags the
reference voltage (Upol = -U2)
ö
÷
÷
×
B
k
÷
÷
ø
Section 9
Current protection
(Equation 194)
355