7.1.4.3
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
are increased √3 times (1.732 times) in comparison with star connected CTs
lead by 30° the primary winding currents (this CT connection rotates currents by
30° in anti-clockwise direction)
do not contain zero sequence current component
For DAB delta connected main CT ratio shall be set for √3 times smaller in RET 670
then the actual ratio of individual phase CTs. The "StarPoint" parameter, for this
particular connection shall be set ToObject. It shall be noted that delta DAB connected
main CTs must be connected exactly as shown in figure 54.
For more detailed info regarding CT data settings please refer to the three application
examples presented in section

Application Examples

Three application examples will be given here. For each example two differential
protection solutions will be presented:
First solution will be with all main CTs star connected.
Second solution will be with delta connected main CT on Y (that is, star)
connected sides of the protected power transformer.
For each differential protection solution the following settings will be given:
1.
Input CT channels on the transformer input modules.
2.
General settings for the transformer differential protection where specific data
about protected power transformer shall be entered.
Finally the setting for the differential protection characteristic will be given for all
presented applications.
Example 1: Star-delta connected power transformer without on-load
tap-changer
Single line diagrams for two possible solutions for such type of power transformer
with all relevant application data are given in figure 55.
Differential protection
"Application
Examples".