Generator Continuous Unbalance Current Capability - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
9.12.2.2
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Generator continuous unbalance current capability

During unbalanced loading, negative sequence current flows in the stator winding.
Negative sequence current in the stator winding will induce double frequency current
in the rotor surface and cause heating in almost all parts of the generator rotor.
When the negative sequence current increases beyond the generator's continuous
unbalance current capability, the rotor temperature will increase. If the generator is
not tripped, a rotor failure may occur. Therefore, industry standards has been
established that determine generator continuous and short-time unbalanced current
capabilities in terms of negative sequence current I
Typical short-time capability (referred to as unbalanced fault capability) expressed in
terms of rotor heating criterion
Table 43:
ANSI requirements for unbalanced faults on synchronous machines
Types of Synchronous Machine
Salient pole generator
Synchronous condenser
Cylindrical rotor generators:
Fig
201
shows a graphical representation of the relationship between generator
capability and generator MVA rating for directly cooled (conductor cooled)
generators. For example, a 500 MVA generator would have K = 10 seconds and a 1600
MVA generator would have K = 5 seconds. Unbalanced short-time negative sequence
current I
is expressed in per unit of rated generator current and time t in seconds.
2
and rotor heating criteria
2
2
=
I t
K
is shown below in Table 43.
2
Indirectly cooled
Directly cooled (0 – 800 MVA)
Directly cooled (801 – 1600
MVA)
Section 9
Current protection
I t
2
[ ]
2
=
I t
K s
2
Permissible
40
30
30
10
See Figure
201
I t
2
2
.
2
389

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents