Connection examples for high impedance differential
protection
WARNING! USE EXTREME CAUTION! Dangerously high
voltages might be present on this equipment, especially on the plate
with resistors. De-energize the primary object protected with this
equipment before connecting or disconnecting wiring or performing
any maintenance. The plate with resistors should be provided with a
protective cover, mounted in a separate box or in a locked cubicle.
National law and standards shall be followed.
Connections for three-phase high impedance differential protection
Generator, reactor or busbar differential protection is a typical application for three-
phase high impedance differential protection. Typical CT connections for three-phase
high impedance differential protection scheme are shown in figure 61.
L1
L2
L3
(A)
(B)
(C)
CT 1200/1
Star/Wye
Connected
Protected Object
CT 1200/1
Star/Wye
Connected
L1
L2
L3
(A)
(B)
(C)
IEC07000193 V5 EN
Figure 61:
CT connections for high impedance differential protection
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
7
1
2
3
4
5
6
7
8
9
1
0
1
1
1
1
2
N
L3 (C)
L2 (B)
L1 (A)
N
L3 (C)
L2 (B)
L1 (A)
X1
11
12
13
2
3
3-Ph Plate with Metrosils and Resistors
1MRK 502 071-UEN -
SMAI2
BLOCK
G2AI3P
AI01
REVROT
G2AI1
(I)
^GRP2L1
G2AI2
^GRP2L2
G2AI3
AI02
^GRP2L3
G2AI4
(I)
^GRP2N
G2N
AI03
(I)
AI04
(I)
AI05
(I)
AI06
(I)
IED
4
5
1
2
3
4
5
6
7
14
X
X
6
IEC07000193-5-en.vsdx
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents