ABB REG670 Applications Manual page 474

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
System protection and control
468
In order to adapt to the previous relay characteristic the above equation can be re-
written in the following way:
æ
K
ç
ç
I
[ ]
=
+
s
so
T
t
ç
1
æ
ö
I
ç
-
0
s
ç
÷
ç
I
è
ø
è
so
EQUATION13000032 V1 EN
Thus if the following rules are followed when multi-purpose overcurrent stage one is
set:
in >
= I
= 300A
S0
K
35566
=
=
=
A
I
300
so
=
0.64
=
B
T
01
C =
0.0
p =
1.0
k =
1.0
then exact replica of the existing relay will be achieved. The following table
summarizes all required settings for the multi-purpose function:
Setting Group1
Operation
CurrentInput
IBase
VoltageInput
UBase
OPerHarmRestr
I_2ndI_fund
BlkLevel2nd
EnRestrainCurr
RestrCurrInput
RestrCurrCoeff
RCADir
ROADir
LowVolt_VM
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
ö
÷
÷
×
1
÷
01
÷
÷
ø
118.55
On
MaxPh
1000
MaxPh
20.50
Off
20.0
5000
Off
PosSeq
0.00
-75
75
0.5
1MRK 502 071-UEN -
(Equation 260)
Application manual