1MRK 502 071-UEN -
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
2
UBase
400
=
=
ZBase
SBase
1000
EQUATION1960 V1 EN
=
+
ZA
Z line
(
)
Zsc station
(
EQUATION1961 V1 EN
This corresponds to:
+
2
j
52
=
=
ZA
0.0125
160
EQUATION1962 V1 EN
Set ZA to 0.32.
=
=
ZB
Zsc station
(
1)
EQUATION1963 V1 EN
This corresponds to:
j
32
=
=
ZB
j
0.20
pu
160
EQUATION1964 V1 EN
Set ZB to 0.2
This corresponds to:
+
2
j
20
=
=
ZC
0.0125
160
EQUATION1966 V1 EN
Set ZC to 0.13 and AnglePhi to 88°
The warning angle (StartAngle) should be chosen not to cross into normal operating
area. The maximum line power is assumed to be 2000 MVA. This corresponds to
apparent impedance:
2
2
U
400
=
=
=
Z
80
S
2000
EQUATION1967 V1 EN
2
=
160
ohm
400
= +
+
2)
2
j
20
j
5000
+
=
j
0.325
pu
0.325 88
2
400
=
j
j
32
ohm
5000
=
Ð °
0.20 90
pu
+
=
j
0.125
pu
0.126 84
ohm
Section 8
Impedance protection
2
= +
2
j
52
ohm
Ð °
pu
Ð °
pu
(Equation 151)
(Equation 152)
(Equation 153)
(Equation 154)
(Equation 155)
(Equation 156)
(Equation 157)
269