ABB REG670 Applications Manual page 558

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 15
Control
552
TR1ATCC then compares this voltage with the set voltage, USet and decides which
action should be taken. To avoid unnecessary switching around the setpoint, a
deadband (degree of insensitivity) is introduced. The deadband is symmetrical around
USet, see figure 282, and it is arranged in such a way that there is an outer and an inner
deadband. Measured voltages outside the outer deadband start the timer to initiate tap
commands, whilst the sequence resets when the measured voltage is once again back
inside the inner deadband. One half of the outer deadband is denoted ΔU. The setting
of ΔU, setting Udeadband should be set to a value near to the power transformer's tap
changer voltage step (typically 75–125% of the tap changer step).
*)
*)
Raise Cmd
0
Ublock
Umin
*) Action in accordance with setting
IEC06000489 V2 EN
Figure 282:
Control actions on a voltage scale
During normal operating conditions the busbar voltage U
deadband (interval between U1 and U2 in figure 282). In that case no actions will be
taken by TR1ATCC. However, if U
appropriate raise or lower timer will start. The timer will run as long as the measured
voltage stays outside the inner deadband. If this condition persists longer than the
preset time delay, TR1ATCC will initiate that the appropriate ULOWER or URAISE
command will be sent from TCMYLTC or TCLYLTC function block to the
transformer tap changer. If necessary, the procedure will be repeated until the
magnitude of the busbar voltage again falls within the inner deadband. One half of the
inner deadband is denoted ΔU
should be set to a value smaller than ΔU. It is recommended to set the inner deadband
to 25-70% of the ΔU value.
This way of working is used by TR1ATCC while the busbar voltage is within the
security range defined by settings Umin and Umax.
A situation where U
falls outside this range will be regarded as an abnormal situation.
B
When U
falls below setting Ublock, or alternatively, falls below setting Umin but still
B
above Ublock, or rises above Umax, actions will be taken in accordance with settings
for blocking conditions (refer to table 59).
If the busbar voltage rises above Umax, TR1ATCC can initiate one or more fast step
down commands (ULOWER commands) in order to bring the voltage back into the
security range (settings Umin, and Umax). The fast step down function operation can
be set in one of the following three ways: off /auto/auto and manual, according to the
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Security Range
D U
D
U
Lower Cmd
DU
DU
in
in
U
U
Uset
Umax
1
2
becomes smaller than U1, or greater than U2, an
B
. The inner deadband ΔU
in
1MRK 502 071-UEN -
*)
Voltage Magnitude
IEC06000489_2_en.vsd
, stays within the outer
B
, setting UDeadbandInner
in
Application manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents