Section 4 Protection Functions; Current Protection; Three-Phase Non-Directional Overcurrent Protection 51P/50P; Identification - ABB RELION REF615R Technical Manual

Hide thumbs Also See for RELION REF615R:
Table of Contents

Advertisement

1MRS240050-IB C
Section 4
4.1
4.1.1
4.1.1.1
4.1.1.2
4.1.1.3
REF615R
Technical Manual
Protection functions

Current protection

Three-phase non-directional overcurrent protection 51P/50P

Identification

Function description
Three-phase non-directional
overcurrent protection, low stage
Three-phase non-directional
overcurrent protection, high stage
Three-phase non-directional
overcurrent protection, instantaneous
stage

Function block

A070553-ANSI V1 EN
Figure 53:
Function block

Functionality

The three-phase overcurrent protection function 51P/50P is used as one-phase, two-phase
or three-phase non-directional overcurrent and short-circuit protection.
The function picks up when the current exceeds the set limit. The trip time characteristics
for low stage 51P and high stage 50P-1/2 can be selected to be either definite time (DT) or
inverse definite minimum time (IDMT). The instantaneous stage 50P-3 always trips with
the DT characteristic.
IEC 61850
IEC 60617
identification
identification
PHLPTOC
3I>
PHHPTOC
3I>>
PHIPTOC
3I>>>
Section 4
Protection functions
ANSI/IEEE C37.2
device number
51P
50P-1/2
50P-3
113

Advertisement

Table of Contents
loading

Table of Contents