also be set to Off, which means no operator place selected that is, operation is not
possible either from local or from remote.
For IEC 61850-8-1 communication, the Bay Control function can be set to
discriminate between commands with orCat station and remote (2 and 3). The
selection is then done through the IEC 61850-8-1 edition 2 command LocSta.
QCBAY also provides blocking functions that can be distributed to different
apparatuses within the bay. There are two different blocking alternatives:
Blocking of update of positions
Blocking of commands
IEC13000016 V2 EN
Figure 235:
APC - Local remote function block

Switch controller SCSWI

SCSWI may handle and operate on one three-phase device or three one-phase
switching devices.
After the selection of an apparatus and before the execution, the switch controller
performs the following checks and actions:
Section 15
Control
IEC13000016-2-en.vsd