ABB REG670 Applications Manual page 367

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Source impedance
Z
(pos. seq)
sc
Z
(pos. seq)
T,1
Z
(zero seq)
T,0
3I
0
Phase to earth fault
IEC06000654 V1 EN
Figure 190:
Equivalent of power system for calculation of setting
The residual fault current can be written:
3U
=
phase
3I
0
×
+
+ ×
2 Z
Z
3 R
1
0
f
EQUATION1948 V1 EN
Where
U
is the phase voltage in the fault point before the fault
phase
Z
is the total positive sequence impedance to the fault point. Z
1
Z
is the total zero sequence impedance to the fault point. Z
0
R
is the fault resistance.
f
The residual voltages in stations A and B can be written:
(
=
×
+
U
3I
Z
3R
0 A
0
T ,0
N
EQUATION1949 V1 EN
=
×
+
U
3I (Z
3R
OB
0
T ,0
N
EQUATION1950 V1 EN
R
N
U
Substation A
0A
Z
(pos. seq)
lineAB,1
Z
(zero seq)
lineAB,0
U
Substation B
0B
Z
(pos. seq)
lineBC,1
Z
(zero seq)
lineBC,0
en06000654.vsd
)
+
Z
)
lineAB,0
Section 9
Current protection
(Equation 200)
= Z
+Z
+Z
+Z
1
sc
T,1
lineAB,1
lineBC,1
= Z
+3R
+Z
+Z
0
T,0
N
lineAB,0
lineBC,0
(Equation 201)
(Equation 202)
361