Section 15
Control
15.3.2.2
516
QB1
QB2
QC1
QA1
QC2
QB9
IEC04000478 V1 EN
Figure 242:
Switchyard layout ABC_LINE
The signals from other bays connected to the module ABC_LINE are described
below.

Signals from bypass busbar

To derive the signals:
Signal
BB7_D_OP
All line disconnectors on bypass WA7 except in the own bay are open.
VP_BB7_D
The switch status of disconnectors on bypass busbar WA7 are valid.
EXDU_BPB
No transmission error from any bay containing disconnectors on bypass busbar WA7
These signals from each line bay (ABC_LINE) except that of the own bay are needed:
Signal
QB7OPTR
Q7 is open
VPQB7TR
The switch status for QB7 is valid.
EXDU_BPB
No transmission error from the bay that contains the above information.
For bay n, these conditions are valid:
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
WA1 (A)
WA2 (B)
WA7 (C)
QB7
QC9
en04000478.vsd
1MRK 502 071-UEN -
Application manual