7.4.2.2
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual

Transformer winding, earthed through zig-zag earthing transformer

A common application is for low reactance earthed transformer where the earthing is
through separate zig-zag earthing transformers. The fault current is then limited to
typical 800 to 2000 A for each transformer. The connection for this application is
shown in figure 73.
- 1
REFPDIF
I3PW1CT1
IdN/I
I3P
- 2
REFPDIF
I3PW2CT1
IdN/I
I3P
IEC09000110-4-EN V2 EN
Figure 73:
Connection of the low impedance Restricted earth-fault function
REFPDIF for a zig-zag earthing transformer
Differential protection
Earthing
transformer
Section 7
Protected
winding W1
Protected
winding W2
IEC09000110-4-EN.vsd
177