ABB REG670 Applications Manual page 97

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
In case of a solid earth fault in high impedance earthed or unearthed systems the
primary value of Uo voltage will be equal to:
U
-
Ph
Ph
=
=
U
0
U
-
Ph
E
3
EQUATION1931 V2 EN
Figure
30
gives an overview of required actions by the user in order to make this
measurement available to the built-in protection and control functions within the IED.
Protected Object
L1
L2
L3
R
6.6
kV
3
IEC06000603 V4 EN
Figure 30:
Neutral point connected VT
IED
2
1
Uo
100
V
Section 4
Analog inputs
(Equation 11)
5
3
SMAI2
BLOCK
AI3P
REVROT
AI1
# Not Used
^GRP2L1
AI2
# Not Used
^GRP2L2
AI3
^GRP2L3
AI4
# Not Used
^GRP2N
AIN
4
IEC06000603-4-en.vsdx
91