Signals From Bus-Coupler - ABB REG670 Applications Manual

Relion 670 series generator protection
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 071-UEN -
15.3.2.3
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
QB7OPTR (bay 1)
QB7OPTR (bay 2)
. . .
. . .
QB7OPTR (bay n-1)
VPQB7TR (bay 1)
VPQB7TR (bay 2)
. . .
. . .
VPQB7TR (bay n-1)
EXDU_BPB (bay 1)
EXDU_BPB (bay 2)
. . .
. . .
EXDU_BPB (bay n-1)
IEC04000477 V1 EN
Figure 243:
Signals from bypass busbar in line bay n

Signals from bus-coupler

If the busbar is divided by bus-section disconnectors into bus sections, the busbar-
busbar connection could exist via the bus-section disconnector and bus-coupler within
the other bus section.
Section 1
(WA1)A1
(WA2)B1
(WA7)C
ABC_LINE
IEC04000479 V1 EN
Figure 244:
Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL
A bus-coupler connection exists between busbar WA1 and WA2.
BC_17_OP
No bus-coupler connection between busbar WA1 and WA7.
BC_17_CL
A bus-coupler connection exists between busbar WA1and WA7.
BC_27_OP
No bus-coupler connection between busbar WA2 and WA7.
BC_27_CL
A bus-coupler connection exists between busbar WA2 and WA7.
VP_BC_12
The switch status of BC_12 is valid.
VP_BC_17
The switch status of BC_17 is valid.
VP_BC_27
The switch status of BC_27 is valid.
EXDU_BC
No transmission error from any bus-coupler bay (BC).
&
&
&
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BC
ABC_LINE
Section 15
Control
BB7_D_OP
VP_BB7_D
EXDU_BPB
en04000477.vsd
Section 2
A2
B2
C
ABC_BC
en04000479.vsd
517

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents