1MRK 502 071-UEN -
7.3.3.4
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Application manual
Angle could not be
measured. One or both
currents too small
180 deg
External fault
region
The characteristic is defined by the
settings:
IMinNegSeq and NegSeqROA
IEC06000433 V2 EN
Figure 70:
NegSeqROA: NegSeqROA determines the boundary between the
internal- and external fault regions

Open CT detection

The Generator differential function has a built-in, advanced open CT detection
feature. This feature can block the unexpected operation created by the Generator
differential function in case of open CT secondary circuit under normal load
condition. An alarm signal can also be issued to station operational personnel to make
remedy action once the open CT condition is detected.
The following setting parameters are related to this feature:
Setting parameter OpenCTEnable enables/disables this feature
Setting parameter tOCTAlarmDelay defines the time delay after which the alarm
signal will be given
Setting parameter tOCTReset defines the time delay after which the open CT
condition will reset once the defective CT circuits have been rectified
Once the open CT condition has been detected, then all the differential protection
functions are blocked except the unrestraint (instantaneous) differential
protection
The outputs of open CT condition related parameters are listed below:
90 deg
120 deg
270 deg
Section 7
Differential protection
NegSeqROA
(Relay Operate Angle)
Internal fault
region
0 deg
IminNegSeq
Internal /
external fault
boundary.
Default ± 60 deg
en06000433-2.vsd
173