Event Function Event - ABB Relion 650 Series Communication Protocol Manual

Spa
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 3
SPA operation principle
#CD01-CMDOUT1
#CD01-CMDOUT2
#CD01-CMDOUT3
#CD01-CMDOUT4
#CD01-CMDOUT5
#CD01-CMDOUT6
#CD01-CMDOUT7
#CD01-CMDOUT8
#CD01-CMDOUT9
#CD01-CMDOUT10
#CD01-CMDOUT11
#CD01-CMDOUT12
#CD01-CMDOUT13
#CD01-CMDOUT14
#CD01-CMDOUT15
#CD01-CMDOUT16
IEC05000717 V4 EN-US
Figure 3:
The MODE input defines if the output signals from SINGLECMD:1 is off, steady or setable pulse
length signals. This is set in Parameter Setting Tool (PST) under: Main Menu/Settings / IED
Settings / Control / Commands / Single Command or via Parameter Setting Tool (PST).
3.1.2.3

Event function EVENT

The Event function (EVENT) sends time-tagged events to the station level (for example,
operator workplace) over the station bus. On the station level, events are presented in an
event list. Events can be created from both internal logical signals and binary input channels.
All the internal signals are time tagged in the main processing module, while the binary input
channels are time tagged directly on each I/O module. Events are produced according to a set
of event masks. These masks are treated commonly for both LON and SPA channels. All events
according to the event mask are stored in a buffer which contains up to 1000 events. If new
events appear before the oldest event in the buffer is read, the oldest event is overwritten and
an overflow alarm appears.
Two special signals for event registration purposes are available in the IED: Terminal Restarted
(0E50) and Event buffer overflow (0E51).
Input parameters can be set individually from the Parameter Setting Tool (PST) under: Main
Menu/Settings / IED Settings / Monitoring / Event Function or via the Parameter Setting
Tool (PST) as follows:
No events
OnSet, at pick-up of the signal
OnReset, at drop-out of the signal
OnChange, at both pick-up and drop-out of the signal
AutoDetect, the EVENT function makes the reporting decision (reporting criteria for
integers has no semantic, prefer to be set by the user)
For double indications, only the fist eight inputs, 1–8, must be used. Inputs 9–16 can be used
for other types of events in the same EVENT block.
Status and event codes for the EVENT function are found in Table 3.
14
SINGLECMD
BLOCK
^OUT1
^OUT2
^OUT3
^OUT4
^OUT5
INPUT1
^OUT6
INPUT2
^OUT7
INPUT3
^OUT8
INPUT4
^OUT9
^OUT10
^OUT11
^OUT12
^OUT13
^OUT14
^OUT15
^OUT16
SYNCH OK
Application example showing a simplified logic diagram for control of a
circuit breaker
INPUT
AND
OUT
INPUT
NOUT
1MRK 511 379-UEN A
PULSETIMER
OUT
To output board, CLOSE
PULSETIMER
To output board, OPEN
OUT
IEC05000717-4-en.vsd
Communication protocol manual
M11880-82 v5

Advertisement

Table of Contents
loading

Table of Contents