Timeprovider 5000 Power Connector; Tp E10 And Tp E30 - Power Connector A; Tp E10 And Tp E30 - Power Connector B - Symmetricom TimeProvider 5000 User Manual

Ieee 1588 grand master clock / ntp server
Hide thumbs Also See for TimeProvider 5000:
Table of Contents

Advertisement

4. Using 1 mm² / 18 AWG (minimum) stranded wire, connect primary power to the
connectors per the polarity markings. Use the polarity markings of "-48V" and
"RTN" as a reference for the proper polarity connection..
Note: The -48VDC power must be connected with the proper polarity.
The unit will not be damaged by reverse polarity, but the unit will not
operate if the polarity is reversed.
5. Insert the connectors into the power connections in the chassis. See
Figure
2-31. Tighten screws in the connector
Figure 2-31. TimeProvider 5000 Power Connector
Figure 2-32. TP E10 and TP E30 - Power Connector A
Figure 2-33. TP E10 and TP E30 - Power Connector B
098-00028-000 Revision F – May, 2012
Chapter 2 Installing
Making Ground and Power Connections
TimeProvider 5000 User's Guide
87

Advertisement

Table of Contents
loading

Table of Contents