Evaluating Node Status - I/O Led (Blink Code Table); Table 99: Node Status Diagnostics - Solution In Event Of Error - WAGO I/O-SYSTEM 750 Manual

Ethercat fieldbus coupler, id switch 100 mbit/s; digital and analog signals
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-354/000-001 EtherCAT® Fieldbus Coupler, ID Switch
9.1.3
Evaluating Node Status – I/O LED (Blink Code Table)
The communication status between fieldbus coupler/controller and the I/O
modules is indicated by the I/O LED.
Table 99: Node Status Diagnostics – Solution in Event of Error
LED Status
I/O
green
orange
flashing
red
red
flashing
red
cyclical
flashing
off
Device boot-up occurs after turning on the power supply. The I/O LED flashes
orange.
Then the local bus is initialized. This is indicated by flashing red at 10 Hz for
1 ... 2 seconds.
After a trouble-free initialization, the I/O LED is green.
In the event of an error, the I/O LED continues to blink red. Blink codes indicate
detailed error messages. An error is indicated cyclically by up to 3 flashing
sequences.
After elimination of the error, restart the node by turning the power supply of the
device off and on again.
Meaning
The fieldbus node is operating correctly.
Start of the firmware.
1 ... 2 seconds of rapid flashing indicates
start-up.
Fieldbus coupler/controller hardware
defect
Flashing with approx. 10 Hz indicates the
initialization of the local bus or a local bus
error.
Up to three successive flashing
sequences indicate local bus errors.
There are short intervals between the
sequences.
No data cycle on the local bus.
Diagnostics 123
Solution
Normal operation.
-
Replace the fieldbus coupler/controller.
Note the following flashing sequence.
Evaluate the flashing sequences based
on the following blink code table.
The blinking indicates an error message
comprised of an error code and error
argument.
The fieldbus coupler/controller supply is
off.
Version 1.2.1
Manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-354/000-001

Table of Contents