YASKAWA L1000A Technical Manual page 70

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

3.8 Control Circuit Wiring
Type
No.
Power supply for analog inputs
+V
Power supply for analog inputs
-V
A1
Multi-function analog input 1 (Speed reference bias)
Analog Inputs
Multi-function analog input 2 (Not used)
A2
AC
Analog input common
Ground for shielded lines and option cards
E (G)
<1> Setting jumper S3 for an external power supply makes the wire jumper between terminals H1, H2, and HC ineffective. Remove the wire jumper
and connect an external power supply that can supply terminals H1, H2, and HC continuously.
Output Terminals
Table 3.7
lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function
output.
Note: Multi-function relay output terminals are rated at a minimum of 10 mA. If less than 10 mA is required, use the photocoupler
outputs (P1-C1, P2-C2). Using the wrong current output level may cause undesirable effects when the terminal is activated.
Type
No.
N.O.
MA
N.C. output
Fault Relay
MB
Fault output common
MC
M1
Multi-function relay output 1 (Brake release command)
M2
Multi-Function
M3
Relay Output
Multi-function relay output 2 (Output contactor close command)
M4
<1>
M5
Multi-function relay output 3 (Drive ready)
M6
P1
Photocoupler output 1 (During Frequency output)
Multi-Function
C1
Photocoupler
P2
Output
Photocoupler output 2 (Not Used/Through Mode)
C2
Analog monitor output 1 (Output speed)
FM
Monitor Output
Analog monitor output 2 (Output current)
AM
Monitor common
AC
Safety monitor output
DM+
Safety Monitor
Output
DM-
Safety monitor output common
<1> Refrain from assigning functions to terminals M1 thru M6 that involve frequent switching, as doing so may shorten relay performance life.
Switching life is estimated at 200,000 times (assumes 1 A, resistive load).
<2> Connect a suppression diode as shown in
than the circuit voltage.
Figure 3.21
70
Terminal Name (Function)
Table 3.7 Control Circuit Output Terminals
Terminal Name (Function)
Figure 3.17
when driving a reactive load such as a relay coil. Make sure the diode rating is greater
A
A – External power, 48 V max.
B – Suppression diode
Figure 3.17 Connecting a Suppression Diode
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Function (Signal Level) Default Setting
10.5 Vdc (max allowable current 20 mA)
-10.5 Vdc (max allowable current 20 mA)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
-10 to 10 Vdc, 0 to 10 Vdc (input impedance: 20 kΩ)
0 V
Function (Signal Level) Default Setting
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
Contact relay output
30 Vdc, 10 mA to 1 A
250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA
48 Vdc, 2 to 50 mA
<2>
-10 to +10 Vdc or 0 to +10 Vdc
0 V
Outputs status of Safe Disable function. Closed when both Safe Disable
channels are closed. Up to +48 Vdc 50 mA
B
C
YEA_common
D
C – Coil
D – 50 mA or less
Page
148
148
197
148
198
148
Page
188
188
200

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents