5.6 F: Option Settings
No.
F1-04
F1-10
F1-11
Settings for Parameter F1-04:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only (drive continues operating while "dEv" flashes on the screen)
F1-05: Encoder 1 Rotation Direction Selection
Determines the direction indicated by the motor encoder signal.
Refer to
PG Encoder Setup on page 99
No.
F1-05
Setting 0: Phase A leads phase B with an Up command.
Setting 1: Phase B leads phase A with an Up command.
F1-06: PG1 Pulse Monitor Output Division Ratio
Sets the ratio between the pulse input and the pulse output of a speed feedback option card as a three digit number, where
the first digit (n) sets the numerator and the second and third digit (m) set the denominator as shown below:
(1 + n)
f
= f
Pulse Input
Pulse Output
Example: To have a ratio of 1/32 between the speed feedback option card pulse input and output, set F1-06 = 032.
No.
F1-06
F1-18: dv3 Detection Selection (CLV/PM)
Sets the number of times the drive will detect a dv3 situation before triggering a dv3 fault. The drive detects a dv3
condition when the torque reference and speed reference are in opposite directions while the difference between the actual
motor speed and the speed reference is greater than 30%. Setting F1-18 to 0 disables dv3 detection.
No.
F1-18
Note: A common cause for a dv3 fault is the incorrect setting of E5-11. Make sure the correct encoder offset has been entered to E5-11.
F1-19: dv4 Detection Selection (CLV/PM)
Sets the number of pulses necessary to trigger a dv4 fault when there is a motor speed deviation opposite to the frequency
reference. Setting F1-19 to 0 disables dv4 detection.
No.
F1-19
Note: A common cause for a dv4 fault is the incorrect setting of E5-11. Make sure the correct encoder offset is set to E5-11.
178
Parameter Name
Operation Selection at Deviation
Excessive Speed Deviation Detection Level
Excessive Speed Deviation Detection Delay Time
for details on how to set the direction for the encoder and the motor.
Parameter Name
Encoder 1 Rotation Direction Selection
common_TMonly
m
Parameter Name
PG1 Pulse Monitor Output Division Ratio
Parameter Name
dv3 Detection Selection
Parameter Name
dv4 Detection Selection
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Setting Range
0 to 3
0 to 50%
0.0 to 10.0 s
Setting Range
0 or 1
Setting Range
1
1 to 132 (1 to
)
32
Setting Range
0 to 10
Setting Range
0 to 5000
Default
3
10%
0.5 s
Default
Default
1
Default
10
Default
128