7.4 Drive Cooling Fans and Circulation Fans
Installing the Cooling Fan
NOTICE: Prevent Equipment Damage. Follow cooling fan replacement instructions. Improper cooling fan replacement could result in
damage to equipment. When installing the replacement cooling fan into the drive, make sure the fan is facing upwards. To ensure
maximum useful product life, replace all cooling fans when performing maintenance.
Reverse the procedure described above to reinstall the cooling fan.
1.
Install the replacement fan into the drive, ensuring the alignment pins line up as shown in the figure below.
Figure 7.4
A – Push the connectors together
B – Label facing up
Figure 7.4 Installing the Cooling Fan: 2A0018 to 2A0075, 4A0009 to 4A0039
2.
Properly connect the fan power lines, then place the cable back into the recess of the drive.
Figure 7.5
YEA_
TMon
ly
Figure 7.5 Cooling Fan Power Supply Connectors: 2A0018 to 2A0075, 4A0009 to 4A0039
3.
While pressing in on the hooks on the left and right sides of the fan finger guard, guide the fan finger guard until it
clicks back into place.
Figure 7.6
4.
Turn the power supply back on and reset the cooling fan operation time for the Maintenance Monitor by setting
o4-03 to 0.
296
YEA_
TMon
ly
A
completely
A – Back
YEA_TMo
nly
Figure 7.6 Reattach the Fan Cover: 2A0018 to 2A0075, 4A0009 to 4A0039
B
C – Make sure the pins align
properly.
B – Front
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual