C.9 MEMOBUS/Modbus Data Table
Register No.
Communications Error Contents
bit 0
bit 1
bit 2
003DH
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
003EH
Output Speed
003FH
0040H to 004AH
Used for various monitors U1-
Drive status (U1-12)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
004BH
bit 7
bit 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
004CH to 007EH
Used for various monitors U1-
007FH
Alarm Code, Refer to Alarm Register Contents on page 407 for alarm codes.
Used for monitors U2-
0080H to 0097H
descriptions.
0098H
High Word of Accumulated Operation Time Monitor, 10h units (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor, 1h units (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
00ACH
Speed Feedback (U1-05)
00ADH
00AEH, 00AFH
Reserved
00B0H
Option Code Connected to CN5-A
00B1H
Reserved
00B2H
Option Code Connected to CN5-B
00B3H
Option Code Connected to CN5-C
00B4H
Reserved
00B5H
Output Speed After Soft Start
(U1-16)
00B6H
00B7H
Speed Reference
00B8H
00B9H to 00BEH
Reserved
00BFH
Lists the last to digits of operation error code oPE
400
<3>
CRC Error
Data Length Error
Reserved
Parity Error
Overrun Error
Framing Error
Timeout
Reserved
r/min
<4>
0.01% units
. Refer to U: Monitors on page 372 for parameter details.
During Run
During Zero Speed
During Reverse Run
During Fault Reset Signal Input
During Speed Agree
Drive Ready
Alarm
Fault
During Operation Error (oPE
During Momentary Power Loss
Motor 2 Selected
Reserved
Reserved
Reserved
ComRef status, NetRef status
ComCtrl status, NetCtrl status
, U4-
, and U6-
. Refer to U: Monitors on page 372 for parameter details.
, U3-
. Refer to U: Monitors on page 372 for parameter details and Refer to Fault Trace Contents on page 406 for register value
<2>
r/min units
<4>
0.01% units
Register contains ASCII code of the option card.
DI-A3 = 0x01
DO-A3 = 0x02
AO-A3 = 0x04
PG-B3 = 0x11
PG-X3 = 0x12
PG-F3 = 0x21
PG-E3 = 0x22
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type number.
Example: Register value is 5353H for "SS" if a SI-S3 option card is installed.
r/min units
<4>
0.01% units
r/min units
<4>
0.01% units
.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual