YASKAWA L1000A Technical Manual page 109

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.
The display automatically returns to the display in Step 1.
Repeat Steps 1 through 5 to set the following parameters:
• T1-03, Motor Rated Voltage
• T1-04, Motor Rated Current
6.
• T1-05, Motor Base Frequency
• T1-06, Number of Motor Poles
• T1-07, Motor Base Speed
Note:
Refer to Parameter Settings during Induction Motor Auto-Tuning: T1 on page 110
Starting Auto-Tuning
WARNING! Sudden Movement Hazard. The drive and motor may start unexpectedly during Auto-Tuning, which could result in death or
serious injury. Ensure the areas surrounding the drive, motor and load are clear before proceeding with Auto-Tuning.
WARNING! Electrical Shock Hazard. High voltage will be supplied to the motor when Stationary Auto-Tuning is performed even with
the motor stopped, which could result in death or serious injury. Do not touch the motor until Auto-Tuning has been completed.
WARNING! When performing Rotational Auto-Tuning for motor data or PG encoder offset, always uncouple the motor from the
mechanical system (remove ropes from traction sheave). Performing Rotational Auto-Tuning with the mechanical system connected to
the motor can cause hazardous situations, injury to personnel and damage to the equipment.
NOTICE: Rotational Auto-Tuning will not function properly if a holding brake is applied on the load. Ensure the motor can freely spin
before beginning Auto-Tuning. Failure to comply could result in improper operation of the drive.
Enter the required information from the motor nameplate. Press
Note: These instructions continue from Step 6 in "Enter Data from the Motor Nameplate".
1.
After entering the data listed on the motor nameplate, press
Press
to activate Auto-Tuning. The drive begins by injecting current into the motor for about 1 min,
and then starts to rotate the motor.
2.
Note: The first digit on the display indicates which motor is undergoing Auto-Tuning (motor 1 or motor 2). The
second digit indicates the type of Auto-Tuning being performed.
3.
Auto-Tuning finishes in approximately one to two minutes.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Step
Step
to confirm.
- A.TUNE -
T1-02= 4.00kW
for details.
to proceed to the Auto-Tuning start display.
4.5 Auto-Tuning
Display/Result
PRG
Mtr Rated Power
(0.00 ~ 650.00)
"3.70kW"
ESC
FWD
DATA
- A.TUNE -
PRG
Mtr Rated Power
T1-02= 4.00kW
(0.00 ~ 650.00)
"3.70kW"
ESC
FWD
DATA
- A.TUNE -
PRG
Rated Speed
T1-07= 1450RPM
(0 ~ 24000)
"1450RPM"
ESC
FWD
DATA
Display/Result
- A.TUNE -
DRV
Auto-Tuning
0.00 Hz/ 0.00A
Tuning Ready ?
Press RUN key
ESC
FWD
- A.TUNE -
DRV
Rdy
Tune Proceeding
X.XX Hz/ X.XXA
FWD
- MODE -
DRV
End
Tune Successful
FWD
RESET
109