YASKAWA L1000A Technical Manual page 240

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.11 S: Elevator Parameters
Leveling Speed
Input Timing
Constant speed
operation at
rated speed
(normal stop
sequence)
(The speed is 40% of the nominal speed or more.)
Operating
speed
0
H1-
= 53
(Leveling Speed)
During
acceleration
(The speed is less than 40% of the nominal speed.)
Operating
speed
0
H1-
= 53
(Leveling Speed)
(The speed is 40% of the nominal speed or more.)
Operating
speed
0
H1-
= 53
Constant speed
(Leveling Speed)
operation at
less than the
(The speed is less than 40% of the nominal speed.)
rated speed
Operating
speed
0
H1-
= 53
(Leveling Speed)
Before start
240
Table 5.14 Short Floor Operation Example
Short Floor
Operating
speed
0
H1-
= 53
(Leveling Speed)
d1-19
(Nominal Speed)
40% of nominal
speed
d1-26
(Leveling Speed)
Time
ON(close)
d1-19
(Nominal Speed)
40% of nominal
speed
d1-26
(Leveling Speed)
Time
ON(close)
d1-19
(Nominal Speed)
40% of nominal
speed
d1-26
(Leveling Speed)
Time
ON(close)
d1-19
(Nominal Speed)
40% of nominal
speed
d1-26
(Leveling Speed)
Time
ON(close)
Operates at the leveling speed.
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Advanced Short Floor
d1-19
(Nominal Speed)
d1-26
(Leveling Speed)
Time
ON(close)
(The speed is over Optimum Speed.)
Operating
speed
0
H1-
= 53
ON(close)
(Leveling Speed)
(The speed is optimal speed or less.)
Operating
speed
S5-03
0
H1-
= 53
ON(close)
(Leveling Speed)
Not Available.
d1-19
(Nominal Speed)
Optimal Speed
d1-26
(Leveling Speed)
Time
d1-19
(Nominal Speed)
Optimal Speed
d1-26
(Leveling Speed)
Time