YASKAWA L1000A Technical Manual page 357

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

H3-
Function
Setting
Speed Reference Bias
0
(value added to input signal when multiple
analog terminals supply the speed reference)
Auxiliary Speed Reference 1 (used as a second
2
speed reference)
Auxiliary Speed Reference 2 (used as third
3
speed reference)
14
Torque Compensation (load cell input)
1F
Not used (Through Mode)
H4: Analog Outputs
No.(Addr.)
Name
H4-01
Terminal FM Monitor Selection
(41DH)
H4-02
(41EH)
Terminal FM Gain
H4-03
(41FH)
Terminal FM Bias
H4-04
Terminal AM Monitor Selection
(420H)
H4-05
(421H)
Terminal AM Gain
H4-06
(422H)
Terminal AM Bias
H4-07
Terminal FM Signal Level
(423H)
Selection
H4-08
Terminal AM Signal Level
(424H)
Selection
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
H3 Multi-Function Analog Input Settings
All Modes
10 V = E1-04 (maximum output frequency)
All Modes
10 V = E1-04 (maximum output frequency)
All Modes
10 V = E1-04 (maximum output frequency)
V/f
OLV
10 V = Motor rated torque
All Modes
Sets this value when using the terminal in the pass-through mode.
Description
All Modes
Selects the data to be output through multi-function analog output terminal FM.
Set the desired monitor parameter to the digits available in U -
for U1-03.
All Modes
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
All Modes
Sets the bias value added to the terminal FM output signal.
All Modes
Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U -
for U1-03.
All Modes
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value.
All Modes
Sets the bias value added to the terminal AM output signal.
All Modes
0: 0 to 10 V
1: –10 to 10 V
All Modes
0: 0 to 10 V
1: –10 to 10 V
B.3 Parameter Table
Description
CLV
CLV/PM
common_
TMonly
Default: 102
Min: 000
. For example, enter "103"
Max: 999
Default: 100.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
common_
Default: 0.0%
TMonly
Min: -999.9%
Max: 999.9%
common_
TMonly
Default: 103
Min: 000
Max: 999
. For example, enter "103"
common_
Default: 50.0%
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
common_
Default: 0
TMonly
Min: 0
Max: 1
common_
Default: 0
TMonly
Min: 0
Max: 1
Page
common_
TMonly
199
common_
TMonly
199
common_
TMonly
199
common_
TMonly
199
common_
TMonly
200
Setting
Page
200
200
200
200
200
200
201
201
357