5.11 S: Elevator Parameters
S3-04: Position Lock Bandwidth
Determines the bandwidth around the locked position for a digital output set for H2-
bandwidth) is enabled. The output will be triggered when the car moves from the Position Lock start point to plus or
minus the number of pulses set to S3-04.
No.
S3-04
S3-10: Starting Torque Compensation Increase Time
Sets a time constant for the torque reference to reach 300%. Enabled by setting an analog input terminal for torque
compensation (H3-
= 14).
No.
S3-10
S3-12: Starting Torque Compensation Bias in Down Direction
Adds a bias to torque compensation in Down direction.
Refer to
Adjusting the Torque Compensation at Start on page 121
No.
S3-12
S3-14: Torque Compensation Fade Out Speed
Sets the speed level for torque compensation to fade out during the time determined by S3-15. Set as a percentage of the
maximum output frequency (E1-04). A setting of 0.0% disables this function.
No.
S3-14
S3-15: Torque Compensation Fade Out Time
Sets the time for torque compensation to fade out when motor speed reaches the level set in S3-14.
No.
S3-15
S3-16: Torque Limit Reduction Time
After Position Lock at stop, S3-16 determines the length of time to reduce the torque limit rate =
No.
S3-16
S3-20: Dwell 2 Speed Reference
Sets the speed reference for the Dwell 2 function.
Note: Setting this parameter to 0.00 disables the Dwell 2 function.
No.
S3-20
234
Parameter Name
Position Lock Bandwidth
Parameter Name
Starting Torque Compensation Increase Time
Parameter Name
Starting Torque Compensation Bias in Down Direction
Parameter Name
Torque Compensation Fade Out Speed
Parameter Name
Torque Compensation Fade Out Time
Parameter Name
Torque Limit Reduction Time
Parameter Name
Dwell 2 Speed Reference
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
= 33 (Within position lock
Setting Range
0 to 16383
Setting Range
0 to 5000 ms
for details.
Setting Range
–40.0 to 40.0%
Setting Range
0.0 to 100.0%
Setting Range
0 to 5000 ms
Setting Range
0 to 10000 ms
Setting Range
0.00 to 100.00
Default
10
Default
500 ms
Default
0.00%
Default
0.0%
Default
1000 ms
Torque 300%
S3-16
Default
100 ms
Default
0.00%