YASKAWA L1000A Technical Manual page 167

Ac drive for elevator applications; type: cimr-luxa; 200 v class: 3.7 to 110 kw (5 to 150 hp); 400 v class: 3.7 to 132 kw (5 to 200 hp) a
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

d1-26: Leveling Speed
Sets the inspection speed when a multi-function input terminal is programmed for "Leveling speed" (H1-
No.
d1-26
<1> Setting ranges and defaults vary by the setting units determined by parameter o1-03. Refer to
Selection (o1-03) on page 382
Motor Switch Selection
When an input terminal selects motor 2 (H1-
cannot control motor 2 with OLV, CLV or CLV/PM.
The motor 2 speed reference in d1-27 can also be used to operate motor 1 using V/f Control. Refer to
combinations of selecting the speed reference for motor 2 and the motor 1/2 selection switch. (H1-
Table 5.8 Speed Reference for Motor 2, Controlling Motor 1 and 2
The value set to d1-27
Frequency reference
frequency reference set to
0.00
Motor 1
not 0.00
d1-27
<1> Enter the same values to the E3 and E4 parameters that are set for the E1 and E2 parameters.
d1-27: Motor 2 Speed Reference
Sets the speed reference for motor 2.
No.
d1-27
Note: 1. The drive will control motor 1 when this parameter is set to 0.00.
2. Set the accel/decel times in parameters C1-12 and C1-13 when using motor 2.
3. When motor 2 is selected, the following monitors will display values in Hz: U1-01, U1-02, U1-05, U4-19, U4-20.
d1-28: Leveling Speed Detection Level
When the speed priority selection in d1-18 is set to "0" or "3" and the speed reference value falls below the level set in d1-
28, the drive interprets the selected speed as leveling speed. This parameter must be set to use the Speed Control Loop
setting 3 when d1-18 = 0/3. Refer to
No.
d1-28
d1-29: Inspection Speed Detection Level
When the speed priority selection in d1-18 is set to "0" or "3" and the speed reference value is below the level set in d1-
29 but higher than the level set in d1-28, the drive interprets the selected speed as inspection speed. This parameter must
be set to use the Inspection Operation function when d1-18 = 0/3. Refer to
No.
d1-29
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
Name
Leveling Speed
for details.
= 16), the drive will operate a second motor using V/f Control. The drive
Control mode
Accel/Decel ramp
V/f with motor 1
C1-01 to C1-08
<1>
V/f with motor 2
Name
Motor 2 Speed Reference
C5: Speed Control Loop on page 161
Name
Leveling Speed Detection Level
Name
Inspection Speed Detection Level
0.00 to 100.00%
Defaults and Setting Ranges by Display Unit
S-charactor/ Jerk
C2-01 to C2-05
C1-12/C1-13
N.A.
for details.
Inspection Operation on page 118
5.4 d: Reference Settings
Setting Range
Default
8.00%
<1>
Table 5.8
= 53).
Contactor/
Brake sequence
Available
N.A.
Not for hoist
Setting Range
Default
0.00 to 120.00 Hz
0.00 Hz
Setting Range
Default
0.00 to 100.00%
Setting Range
Default
[d1-28] to 100.00%
= 53).
<1>
for
Purpose
Hoist
5
0.00%
for details.
0.00%
167