5.7 H: Terminal Functions
Figure 5.26
Refer to
L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 206
Setting 1A: During down direction
A digital output set for "During down direction" will close whenever the drive is running the elevator in down direction.
Status
Open
Elevator is being driven in up direction or stopped.
Closed
Elevator is being driven in down direction.
Figure 5.27
During Down Direction
Setting 1B: During baseblock (N.C.)
Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not
switch and no main circuit voltage is output.
Status
Open
Baseblock is being executed.
Closed
Drive is not in a baseblock state.
Setting 1C: Motor 2 selection
Indicates which motor is selected when another output terminal is set up to switch drive operation between two motors
(H1-
= 16). Refer to
Status
Open
Motor 1 is selected.
Closed
Motor 2 is selected.
Setting 1D: During regeneration
Terminal closes when the motor is driven in the regenerative mode.
Setting 1E: Reset enabled
An output set for "Reset enabled" closes when the drive attempts to reset after a fault has occurred.
194
Output speed
or motor speed
Speed
OFF
ON
detection 4
Figure 5.26 Speed Detection 4 Example with Positive L3-04 Value
Output Speed
Up command
Down command
Figure 5.27 Down Direction Output Example Time Chart
Setting 16: Motor 2 selection on page 186
L4-04
L4-03
Description
OFF
ON
Description
for details on switching motors.
Description
YASKAWA ELECTRIC SIEP C710616 38A YASKAWA AC Drive L1000A Technical Manual
common_
TMonly
for more details.
common_
TMonly
time